Обзор
Обзор
Example of Power Module PM250D FSD
The regenerative feedback capability of the PM250D Power Module in generating mode (electronic braking) means that energy is returned to the supply system and not destroyed in a braking resistor. This saves space, time-consuming dimensioning of the braking resistor as well as its wiring. Generated heat is also reduced.
An innovative circuit design reduces supply harmonics. A line reactor is not required. This saves space and costs for engineering and procurement.
The PM250D Power Module is also designed for safety-sensitive applications. In conjunction with a Safety Control Unit, the drive can be turned into a Safety Integrated Drive (see Control Units).
Заказные данные
Заказной № |
Вес, кг |
Описание |
Наличие на складе |
Заказать |
6SL3525-0PE17-5AA0 |
5.7 |
Sinamics g120d power module pm250d with built in cl. a filter possibility of regeneration 3ac380-480v +10/-10% 47-63hz output high overload: 0, 75kw for 200% 3s, 150% 60s, 100% 300s ambient temp -10 to +40 deg c 210 x 450 x 110 (hxwxd), fsa protection ip65 without control unit |
------ |
|
6SL3525-0PE17-5AA1 |
5.7 |
SINAMICS G120D СИЛОВОЙ МОДУЛЬ PM250D ВСТРОЕННЫЙ ФИЛЬТР КЛАССА А, ВОЗМОЖНА РЕКУПЕРАЦИЯ 3-ФАЗН.380-480 В +10/-10% 47-63 ГЦ ВЫСОКИЙ УРОВЕНЬ ПЕРЕГРУЗКИ: 0,75 КВТ ПРИ 200% 3С,150% 60С,100% 300С ТЕМП. ОКР. СРЕДЫ: ОТ -10 ДО +55 ГРАД. C 210 X 450 X 145 (ВХШХГ), Т |
------ |
|
6SL3525-0PE21-5AA0 |
5.7 |
Sinamics g120d power module pm250d with built in cl. a filter possibility of regeneration 3ac380-480v +10/-10% 47-63hz output high overload: 1, 5kw for 200% 3s, 150% 60s, 100% 300s ambient temp -10 to +40 deg c 210 x 450 x 110 (hxwxd), fsa protection ip65 without control unit |
------ |
|
6SL3525-0PE21-5AA1 |
5.7 |
SINAMICS G120D СИЛОВОЙ МОДУЛЬ PM250D ВСТРОЕННЫЙ ФИЛЬТР КЛАССА А, ВОЗМОЖНА РЕКУПЕРАЦИЯ 3-ФАЗН.380-480 В +10/-10% 47-63 ГЦ ВЫСОКИЙ УРОВЕНЬ ПЕРЕГРУЗКИ: 1,5 КВТ ПРИ 200% 3С,150% 60С,100% 300С ТЕМП. ОКР. СРЕДЫ: ОТ -10 ДО +55 ГРАД. C 210 X 450 X 145 (ВХШХГ), ТИ |
------ |
|
6SL3525-0PE23-0AA0 |
8 |
Sinamics g120d power module pm250d with built in cl. a filter possibility of regeneration 3ac380-480v +10/-10% 47-63hz output high overload: 3, 0kw for 200% 3s, 150% 60s, 100% 300s ambient temp -10 to +40 deg c 210 x 450 x 180 (hxwxd), fsb protection ip65 without control unit |
------ |
|
6SL3525-0PE23-0AA1 |
8 |
SINAMICS G120D СИЛОВОЙ МОДУЛЬ PM250D ВСТРОЕННЫЙ ФИЛЬТР КЛАССА А, ВОЗМОЖНА РЕКУПЕРАЦИЯ 3-ФАЗН.380-480 В +10/-10% 47-63 ГЦ ВЫСОКИЙ УРОВЕНЬ ПЕРЕГРУЗКИ: 3,0 КВТ ПРИ 200% 3С,150% 60С,100% 300С ТЕМП. ОКР. СРЕДЫ: ОТ -10 ДО +55 ГРАД. C 210 X 450 X 145 (ВХШХГ), ТИ |
------ |
|
6SL3525-0PE24-0AA0 |
8.5 |
Sinamics g120d power module pm250d with built in cl. a filter possibility of regeneration 3ac380-480v +10/-10% 47-63hz output high overload: 4, 0kw for 200% 3s, 150% 60s, 100% 300s ambient temp -10 to +40 deg c 210 x 450 x 220 (hxwxd), fsc protection ip65 without control unit |
------ |
|
6SL3525-0PE24-0AA1 |
8.5 |
SINAMICS G120D СИЛОВОЙ МОДУЛЬ PM250D ВСТРОЕННЫЙ ФИЛЬТР КЛАССА А, ВОЗМОЖНА РЕКУПЕРАЦИЯ 3-ФАЗН.380-480 В +10/-10% 47-63 ГЦ ВЫСОКИЙ УРОВЕНЬ ПЕРЕГРУЗКИ: 4,0 КВТ ПРИ 200% 3С,150% 60С,100% 300С ТЕМП. ОКР. СРЕДЫ: ОТ -10 ДО +55 ГРАД. C 210 X 450 X 145 (ВХШХГ), ТИ |
------ |
|
6SL3525-0PE25-5AA0 |
8.5 |
Sinamics g120d power module pm250d with built in cl. a filter possibility of regeneration 3ac380-480v +10/-10% 47-63hz output high overload: 5, 5kw for 200% 3s, 150% 60s, 100% 300s ambient temp -10 to +40 deg c 210 x 450 x 220 (hxwxd), fsc protection ip65 without control unit |
------ |
|
6SL3525-0PE25-5AA1 |
8.5 |
SINAMICS G120D СИЛОВОЙ МОДУЛЬ PM250D ВСТРОЕННЫЙ ФИЛЬТР КЛАССА А, ВОЗМОЖНА РЕКУПЕРАЦИЯ 3-ФАЗН.380-480 В +10/-10% 47-63 ГЦ ВЫСОКИЙ УРОВЕНЬ ПЕРЕГРУЗКИ: 5,5 КВТ ПРИ 200% 3С,150% 60С,100% 300С ТЕМП. ОКР. СРЕДЫ: ОТ -10 ДО +55 ГРАД. C 210 X 450 X 145 (ВХШХГ), ТИ |
------ |
|
6SL3525-0PE27-5AA0 |
8.5 |
Sinamics g120d power module pm250d with built in cl. a filter possibility of regeneration 3ac380-480v +10/-10% 47-63hz output high overload: 7, 5kw for 200% 3s, 150% 60s, 100% 300s ambient temp -10 to +40 deg c 210 x 450 x 220 (hxwxd), fsc protection ip65 without control unit |
------ |
|
6SL3525-0PE27-5AA1 |
8.5 |
SINAMICS G120D СИЛОВОЙ МОДУЛЬ PM250D ВСТРОЕННЫЙ ФИЛЬТР КЛАССА А, ВОЗМОЖНА РЕКУПЕРАЦИЯ 3-ФАЗН.380-480 В +10/-10% 47-63 ГЦ ВЫСОКИЙ УРОВЕНЬ ПЕРЕГРУЗКИ: 7,5 КВТ ПРИ 200% 3С,150% 60С,100% 300С ТЕМП. ОКР. СРЕДЫ: ОТ -10 ДО +55 ГРАД. C 210 X 450 X 145 (ВХШХГ), ТИ |
------ |
|
Аксессуары
Заказной № |
Вес, кг |
Описание |
Наличие на складе |
Заказать |
3RK1911-0DB13 |
0.59 |
Energy connection cable single-sided, open on one side Han Q4/2 angled 4 x 4 mm2 Length 1.5 m |
------ |
|
3RK1911-0DB33 |
1.8 |
Energy connection cable single-sided, open on one side Han Q4/2 angled 4 x 4 mm2 Length 5 m |
------ |
|
3RK1911-2BE10 |
2 |
Socket insert Han Q4/2 5 contact sockets 4 mm2, 2 auxiliary contacts 0.5 mm2 pin 11+12 Connector set power supply for connection to MS, RSM of ET200pro, M200D Sleeve housing angled Outgoing unit including screw connection |
------ |
|
3RK1911-2BE30 |
2 |
Socket insert Han Q4/2 5 contact sockets 6 mm2, 2 auxiliary contacts 0.5 mm2 pin 11+12 Connector set power supply for connection to MS, RSM of ET200pro, M200D Sleeve housing angled Outgoing unit including screw connection |
------ |
|
3RK1911-2BE50 |
2 |
Socket insert Han Q4/2 5 contact sockets 2.5 mm2, 2 auxiliary contacts 0.5 mm2 pin 11+12 Connector set power supply for connection to MS, RSM of ET200pro, M200D Sleeve housing angled Outgoing unit including screw connection |
------ |
|
6ES7194-1AB01-0XA0 |
0.228 |
SIMATIC DP, ET200X, СОЕДИНИТЕЛЬ HANQ8 ДЛЯ ПОДКЛЮЧЕНИЯ ДВИГАТЕЛЯ К ПРЕОБРАЗОВАТЕЛЮ ЧАСТОТЫ, DESINA-СОВМЕСТИМЫЙ |
------ |
|
Тех. данные
Интеграция
PM250D Power Modules communicate with the Control Unit via the PM-IF interface.
PM250D Power Modules feature the following interfaces as standard:
- PM‑IF interface for connection of the PM250D Power Module and Control Unit.
- Motor is connected through HAN Q8 (male) including activation of the holding brake and temperature sensor
- Network is connected through HAN Q4/2 (female)
Connection diagram for PM250D Power Module with integrated line filter class A
Технические данные
General technical data
|
PM250D Power Modules
|
Line operating voltage
|
3 AC 380 to 480 V ±10%
|
Line requirements
Line short circuit voltage uk
|
≤ 1%
|
input frequency
|
47 to 63 Hz
|
Output frequency
|
|
|
0 to 650 Hz
|
|
0 to 200 Hz
|
Pulse frequency
|
4 kHz (standard), for higher pulse frequencies, see derating data
|
Power factor
|
0.95
|
Inverter efficiency
|
95 … 97%
|
Control factor
|
87%
|
Overload capability
|
|
|
- Average maximum rated output current during a cycle time of 300 s
- 1.5 × rated output current (i.e. 150 % overload) over 60 s at a cycle time of 300 s
- 2 × rated output current (i.e. 200% overload) over 3 s at a cycle time of 300 s
|
Electromagnetic Compatibility
|
Integrated line filter class A according to EN 55011
|
Possible braking methods
|
Regenerative feedback in generating mode;
integrated braking signal 180 V DC (corresponds to 1 AC 400 V rectified)
|
Degree of protection
|
IP65
|
Operating temperature
|
|
- with standard Control Unit
|
-10 ... +40 °C (14 ... 104 °F) without derating,
> 40 ... 55 °C, see derating characteristics
|
- with fail-safe Control Unit
|
0 ... 40 °C (32 ... 104 °F)
|
Storage temperature
|
-40 ... +70 °C (-40 ... +158 °F)
|
Permitted mounting position
|
Wall mounting and free-standing
|
Relative humidity
|
< 95% RH, non-condensing
|
Cooling
|
FSA and FSB: Convection
FSC: Air cooling as required through built-in fan
|
Installation altitude
|
Up to 1000 m above sea level without derating,
> 1000 m see derating characteristics
|
Standard SCCR (Short Circuit Current Rating) 1)
|
10 kA
|
Protective functions
|
- Undervoltage
- Overvoltage
- Overload
- Ground fault
- Short-circuit
- Stall prevention
- Motor blocking protection
- Motor overtemperature
- Inverter overtemperature
- Parameter interlock
|
Standards conformance
|
UL, cUL, CE, c-tick
|
CE mark
|
To Low-Voltage Directive 73/23/EEC and Machinery Directive 98/37/EEC
|
1) Applies to industrial control cabinet installations to NEC article 409/UL 508A. For further information, visit us on the Internet at:
http://support.automation.siemens.com/WW/view/en/23995621
|
PM250D Power Modules
|
Line voltage
3 AC 380 to 480 V
|
6SL3525-0PE17‑5AA0
|
6SL3525-0PE21‑5AA0
|
6SL3525-0PE23‑0AA0
|
Rated output current Irated1)
|
A
|
2.2
|
4.1
|
7.7
|
Output current Imax
|
A
|
4.4
|
8.2
|
15.4
|
Rated power
|
kW
|
0.75
|
1.5
|
3
|
Rated pulse frequency
|
kHz
|
4
|
4
|
4
|
Efficiency η
|
|
0.97
|
0.97
|
0.97
|
Power loss
|
kW
|
0.047
|
0.061
|
0.103
|
Cooling air requirement
|
m3/s
|
0.004
|
0.005
|
0.009
|
Sound pressure level
|
dB(A)
|
–
|
–
|
–
|
Rated input current 2)
|
A
|
2.1
|
3.8
|
7.2
|
Line supply connection
U1/L1, V1/L2, W1/L3, PE
|
|
HAN Q4/2 (male)
|
HAN Q4/2 (male)
|
HAN Q4/2 (male)
|
|
mm2
|
1.5 … 6
|
1.5 … 6
|
2.5 … 6
|
Motor connection
U2, V2, W2, PE, brake, temperature sensor
|
|
HAN Q8 (female)
|
HAN Q8 (female)
|
HAN Q8 (female)
|
|
mm2
|
1 … 4
|
1 … 4
|
2.5 … 4
|
Motor cable length, max.
|
m
|
15
|
15
|
15
|
Degree of protection
|
|
IP65
|
IP65
|
IP65
|
Dimensions
|
|
|
|
|
|
mm
|
450
|
450
|
450
|
|
mm
|
210
|
210
|
210
|
|
mm
|
110
|
110
|
180
|
Frame size
|
|
FSA
|
FSA
|
FSB
|
Weight, approx.
|
kg
|
5.7
|
5.7
|
8
|
1) The rated output current Irated is based on the loading for high overload (high overload HO).
2) The input current depends on the motor load and line impedance. The input currents apply for rated power loading for a line impedance corresponding to uk = 1%.
|
PM250D Power Modules
|
Line voltage
3 AC 380 to 480 V
|
6SL3525-0PE24‑0AA0
|
6SL3525-0PE25‑5AA0
|
6SL3525-0PE27‑5AA0
|
Rated output current Irated1)
|
A
|
10.2
|
13.2
|
19
|
Output current Imax
|
A
|
20.4
|
26.4
|
38
|
Rated power
|
kW
|
4
|
5.5
|
7.5
|
Rated pulse frequency
|
kHz
|
4
|
4
|
4
|
Efficiency η
|
|
0.97
|
0.97
|
0.97
|
Power loss
|
kW
|
0.141
|
0.209
|
0.295
|
Cooling air requirement
|
m3/s
|
0.012
|
0.018
|
0.025
|
Sound pressure level
|
dB(A)
|
74.5
|
74.5
|
74.5
|
Rated input current 2)
|
A
|
9.5
|
12.2
|
17.7
|
Line supply connection
U1/L1, V1/L2, W1/L3, PE
|
|
HAN Q4/2 (male)
|
HAN Q4/2 (male)
|
HAN Q4/2 (male)
|
|
mm2
|
2.5 … 6
|
4 … 6
|
4 … 6
|
Motor connection
U2, V2, W2, PE, brake, temperature sensor
|
|
HAN Q8 (female)
|
HAN Q8 (female)
|
HAN Q8 (female)
|
|
mm2
|
2.5 … 4
|
4
|
4
|
Motor cable length, max.
|
m
|
15
|
15
|
15
|
Degree of protection
|
|
IP65
|
IP65
|
IP65
|
Dimensions
|
|
|
|
|
|
mm
|
450
|
450
|
450
|
|
mm
|
210
|
210
|
210
|
|
mm
|
220
|
220
|
220
|
Frame size
|
|
FSC
|
FSC
|
FSC
|
Weight, approx.
|
kg
|
8.5
|
8.5
|
8.5
|
1) The rated output current Irated is based on the loading for high overload (high overload HO).
2) The input current depends on the motor load and line impedance. The input currents apply for rated power loading for a line impedance corresponding to uk = 1%.
Дополнительно
Connector sets for the line supply
|
Order No.
|
Connector set for Han Q4/2
power supply
|
|
|
3RK1911-2BE50
|
|
3RK1911-2BE10
|
|
3RK1911-2BE30
|
Pre-assembled motor cables and connector set for the connection between the Power Module and the motor
|
Order No.
|
Pre-assembled motor cable,
with HAN Q8 connector on one end, shielded
|
|
|
6ES7194-1LA01-0AA0
|
|
6ES7194-1LB01-0AA0
|
|
6ES7194-1LC01-0AA0
|
|
6ES7194-1LD01-0AA0
|
Connector set for motor cable,
shielded, HAN Q8
|
6ES7194-1AB01-0XA0
|
Характеристика
Derating data
Pulse frequency
Rated output at 3 AC 400 V
|
Rated output current in A
at a switching frequency of
|
kW
|
hp
|
4 kHz
|
6 kHz
|
8 kHz
|
10 kHz
|
12 kHz
|
14 kHz
|
16 kHz
|
0.75
|
1.0
|
2.2
|
1.9
|
1.5
|
1.3
|
1.1
|
1.0
|
0.9
|
1.5
|
2.0
|
4.1
|
3.5
|
2.9
|
2.5
|
2.1
|
1.8
|
1.6
|
3.0
|
4.0
|
7.7
|
6.5
|
5.4
|
4.6
|
3.9
|
3.5
|
3.1
|
4.0
|
5.0
|
10.2
|
8.7
|
7.1
|
6.1
|
5.1
|
4.6
|
4.1
|
5.5
|
7.5
|
13.2
|
11.2
|
9.2
|
7.9
|
6.6
|
5.9
|
5.3
|
7.5
|
10
|
19
|
16.2
|
13.3
|
11.4
|
9.5
|
8.6
|
7.6
|
Ambient temperature
Installation altitude
Чертеж
Power Module PM250D frame size FSA with integrated line filter class A and plugged-in Control Unit
Power Module PM250D frame size FSB with integrated line filter class A and plugged-in Control Unit
Power Module PM250D frame size FSC with integrated line filter class A and plugged-in Control Unit
Fixing with 4 M5 studs, 4 M5 nuts, 4 M5 washers
Tightening torque: 2.5 Nm (22.1 lbf-in)
Ventilation clearance required (for wall mounting) at top and bottom: 150 mm (5.9 inches)
All dimensions in mm (values in brackets are in inches).
|
|