6ES7 151-8FB00-0AB0
|
Supply voltages
|
|
Rated value
|
|
- [Fehlender Merkmalstext TAK_ABN359_001_000]
|
Yes
|
Current consumption
|
|
Inrush current, max.
|
typ.
|
I²t
|
0.21 A²·s
|
Current output to backplane bus (DC 5 V), max.
|
700 mA
|
from supply voltage 1L+, max.
|
460 mA with DP master module
|
Current consumption/power loss
|
|
Power loss, typ.
|
5.5 W
|
Memory
|
|
Type of storage
|
|
RAM
|
|
|
192 Kibyte; For program and data
|
|
No
|
Load memory
|
|
|
Yes
|
|
8 MByte
|
CPU/blocks
|
|
Number of blocks (total)
|
1 024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the SIMATIC Micro Memory Card used.
|
DB
|
|
|
511; Number range: 1 to 511
|
FB
|
|
|
1 024; Number range: 0 to 2047
|
|
64 Kibyte
|
FC
|
|
|
1 024; Number range: 0 to 2047
|
|
64 Kibyte
|
OB
|
|
|
64 Kibyte
|
Nesting depth
|
|
|
16
|
- additional within an error OB
|
4
|
CPU/processing times
|
|
for bit operations, min.
|
0.1 µs
|
for word operations, min.
|
0.2 µs
|
for fixed point arithmetic, min.
|
2 µs
|
for floating point arithmetic, min.
|
3 µs
|
Times/counters and their remanence
|
|
S7 counter
|
|
|
256
|
|
|
|
Yes
|
|
0
|
|
255
|
|
From Z 0 to Z 7
|
|
|
|
Yes
|
|
0
|
|
999
|
IEC counter
|
|
|
SFB
|
|
Unlimited (limited only by RAM capacity)
|
S7 times
|
|
|
256
|
|
|
|
Yes
|
|
0
|
|
255
|
|
No retentivity
|
|
|
|
10 ms
|
|
9 990 s
|
IEC timer
|
|
|
SFB
|
|
Unlimited (limited only by RAM capacity)
|
Flag
|
|
|
256 byte
|
|
Yes
|
|
MB 0 to MB 15
|
|
8; 1 memory byte
|
Data blocks
|
|
|
511; Number range: 1 to 511
|
|
Yes
|
Local data
|
|
|
510 byte; per priority class
|
Address area
|
|
I/O address area
|
|
|
2 048 byte
|
|
2 048 byte
|
|
|
|
2 048 byte
|
|
2 048 byte
|
Process image
|
|
|
2 048 byte
|
|
2 048 byte
|
|
128 byte
|
|
128 byte
|
Digital channels
|
|
|
16 336
|
|
16 336
|
|
496
|
- Outputs, of which central
|
496
|
Analog channels
|
|
|
1 021
|
|
1 021
|
|
124
|
- Outputs, of which central
|
124
|
Hardware config.
|
|
[Fehlender Merkmalstext TAK_ABN308_001_000]
|
1
|
Number of modules per system, max.
|
63; Centralized
|
Time
|
|
Clock
|
|
- Hardware clock (real-time clock)
|
Yes
|
- buffered and synchronizable
|
Yes
|
|
6 Weeks; At 40 °C ambient temperature, typically
|
|
10 s
|
Operating hours counter
|
|
|
1
|
|
0
|
|
0 to 2^31 hours (when using SFC 101)
|
|
1 hour
|
|
Yes; Must be restarted at each restart
|
Clock synchronization
|
|
|
Yes
|
|
No
|
|
No
|
|
Yes; with DP master module
|
|
Yes; with DP master module
|
|
No
|
|
No
|
|
Yes; as client
|
S7 message functions
|
|
Number of login stations for message functions, max.
|
12
|
Process diagnostic messages
|
Yes; ALARM_S, ALARM_SC, ALARM_SQ, ALARM_D, ALARM_DQ
|
Test commissioning functions
|
|
Status/control
|
|
|
Yes
|
|
Inputs, outputs, memory bits, DB, times, counters
|
- Number of variables, max.
|
30
|
- of which status variable, max.
|
30
|
- of which control variable, max.
|
14
|
Forcing
|
|
|
Yes
|
|
Inputs, outputs
|
- Number of variables, max.
|
10
|
Status block
|
Yes
|
Single step
|
Yes
|
Number of breakpoints
|
2
|
Diagnostic buffer
|
|
|
Yes
|
|
100
|
|
No
|
Communication functions
|
|
PG/OP communication
|
Yes
|
[Fehlender Merkmalstext PMD_ABM308_001_000]
|
Yes
|
Routing
|
Yes
|
Global data communication
|
|
|
No
|
S7 basic communication
|
|
|
Yes; I blocks
|
- Useful data per job, max.
|
76 byte
|
- Useful data per job (of which consistent) max.
|
76 byte
|
S7 communication
|
|
|
Yes
|
|
Yes
|
|
Yes; via integrated PN interface and loadable FBs
|
- Useful data per job, max.
|
180 byte
|
- Useful data per job, of which consistent, max.
|
64 byte
|
S5-compatible communication
|
|
|
No
|
Standard communication (FMS)
|
|
|
No
|
[Fehlender Merkmalstext TAK_ABM372_001_000]
|
|
|
Yes
|
Open IE communication
|
|
|
Yes
|
- Number of connections, max.
|
8
|
- Data length for connection type 01H, max.
|
1 460 byte
|
- Data length for connection type 11H, max.
|
8 192 byte
|
|
Yes
|
- Number of connections, max.
|
8
|
|
8 192 byte
|
|
Yes
|
- Number of connections, max.
|
8
|
|
1 472 byte
|
Number of connections
|
|
|
12
|
- usable for PG communication
|
11
|
- reserved for PG communication
|
1
|
- adjustable for PG communication, min.
|
1
|
- usable for OP communication
|
11
|
- reserved for OP communication
|
1
|
- adjustable for OP communication, min.
|
1
|
- usable for S7 basic communication
|
10
|
- Reserved for S7 basic communication
|
0
|
- adjustable for S7-Basic communication, min.
|
0
|
- usable for S7 communication
|
10
|
- adjustable for S7 communication, max.
|
10
|
- [Fehlender Merkmalstext TAK_ABN313_001_000]
|
32
|
|
4; with DP master module
|
PROFINET CBA (at set setpoint communication load)
|
|
- Setpoint for the CPU communication load
|
50%
|
- Number of remote interconnection partners
|
32
|
- Number of functions, master/slave
|
30
|
- Total of all master/slave connections
|
1 000
|
- Data length of all incoming connections master/slave, max.
|
4 000 byte
|
- Data length of all outgoing connections master/slave, max.
|
4 000 byte
|
- Number of device-internal and PROFIBUS interconnections
|
500
|
- Data length of device-internal and PROFIBUS interconnections, max.
|
4 000 byte
|
- Data length per connection, max.
|
1 400 byte
|
- Remote interconnections with acyclic transmission
|
|
- Number of incoming interconnections
|
100
|
- Number of outgoing interconnections
|
100
|
- Data length of all incoming interconnections, max.
|
2 000 byte
|
- Data length of all outgoing interconnections, max.
|
2 000 byte
|
- Data length per connection, max.
|
1 400 byte
|
- Remote interconnections with cyclic transmission
|
|
- Number of incoming interconnections
|
200
|
- Number of outgoing interconnections
|
200
|
- Data length of all incoming interconnections, max.
|
2 000 byte
|
- Data length of all outgoing interconnections, max.
|
2 000 byte
|
- Data length per connection, max.
|
250 byte
|
- HMI variables via PROFINET (acyclic)
|
|
- Number of log-in stations for HMI variables (PN OPC/iMap)
|
3
|
|
200
|
- Data length of all HMI variables, max.
|
2 000 byte
|
- PROFIBUS proxy functionality
|
|
|
Yes
|
- Number of linked PROFIBUS devices
|
16
|
- Data length per connection, max.
|
240 byte
|
1st interface
|
|
Type of interface
|
PROFINET
|
Physics
|
Ethernet
|
isolated
|
Yes
|
[Fehlender Merkmalstext TAK_ABN325_001_000]
|
Yes
|
[Fehlender Merkmalstext TAK_ABN327_001_000]
|
3
|
1. Schnittstelle
|
Yes
|
1. Schnittstelle
|
Yes
|
Autocrossover
|
Yes
|
Functionality
|
|
|
No
|
|
No
|
|
No
|
|
No
|
|
Yes
|
|
Yes
|
- [Fehlender Merkmalstext TAK_ABN329_001_000]
|
Yes
|
|
No
|
[Fehlender Merkmalstext TAK_ABM367_001_000]
|
|
- [Fehlender Merkmalstext TAK_ABM368_001_000]
|
|
- [Fehlender Merkmalstext PMD_ABM300_001_000]
|
Yes
|
- [Fehlender Merkmalstext PMD_ABM302_001_000]
|
Yes
|
- [Fehlender Merkmalstext PMD_ABM303_001_000]
|
Yes
|
- [Fehlender Merkmalstext TAK_ABN333_001_000]
|
No
|
- [Fehlender Merkmalstext PMD_ABM301_001_000]
|
Yes
|
- [Fehlender Merkmalstext PMD_ABM282_001_000]
|
100 bit/s
|
- Total number of connectable IO Devices, max.
|
128
|
- [Fehlender Merkmalstext TAK_ABN335_001_000]
|
128
|
- [Fehlender Merkmalstext TAK_ABN337_001_000]
|
128
|
- Number of I/O devices with IRT and the option "high flexibility", max.
|
128
|
|
61
|
|
Yes
|
- [Fehlender Merkmalstext PMD_ABM311_001_000]
|
Yes
|
|
32
|
|
Yes
|
|
8
|
|
Yes
|
- [Fehlender Merkmalstext TAK_ABN339_001_000]
|
8
|
- Device replacement without swap medium
|
Yes
|
|
|
|
2 kByte
|
|
254 byte
|
[Fehlender Merkmalstext TAK_ABM366_001_000]
|
|
- [Fehlender Merkmalstext PMD_ABM319_001_000]
|
Yes
|
- [Fehlender Merkmalstext PMD_ABM320_001_000]
|
Yes
|
[Fehlender Merkmalstext TAK_ABM365_001_000]
|
|
- [Fehlender Merkmalstext PMD_ABM304_001_000]
|
Yes
|
|
8
|
2nd interface
|
|
Type of interface
|
External interface via master module 6ES7138-4HA00-0AB0
|
Physics
|
RS 485
|
isolated
|
Yes
|
Power supply to interface (15 to 30 V DC), max.
|
No
|
Functionality
|
|
|
No
|
|
Yes
|
|
No
|
|
No
|
|
No
|
|
No
|
|
No
|
|
No
|
|
No
|
DP master
|
|
- Number of connections, max.
|
12; Notice: 12 connections per CPU, not per interface
|
|
|
|
Yes
|
|
Yes
|
- Global data communication
|
No
|
|
Yes; I blocks only
|
|
Yes
|
- S7 communication, as client
|
No
|
- S7 communication, as server
|
Yes
|
|
Yes
|
|
No
|
|
Yes
|
- Activation/deactivation of DP slaves
|
Yes
|
- direct data exchange (cross traffic)
|
Yes
|
|
Yes
|
- Transmission speeds, max.
|
12 MBit/s
|
- Number of DP slaves, max.
|
32; Per station
|
|
|
|
2 048 byte
|
|
2 048 byte
|
|
|
|
244 byte
|
|
244 byte
|
Isochronous mode
|
|
Isochronouos mode
|
No
|
CPU/programming
|
|
Programming language
|
|
|
Yes; V5.4 SP4
|
|
Yes
|
|
Yes
|
|
Yes
|
|
Yes; Optional
|
|
Yes; optional
|
|
Yes; Optional
|
|
Yes; optional
|
Operational stocks
|
See instruction list
|
Nesting levels
|
8
|
User program protection/password protection
|
Yes
|
System functions (SFC)
|
See instruction list
|
System function blocks (SFB)
|
See instruction list
|
Status information/alarms/diagnostics
|
|
Alarms
|
|
|
Yes
|
Diagnoses
|
|
|
Yes
|
Diagnostics indication LED
|
|
- [Fehlender Merkmalstext TAK_ABN526_001_000]
|
Yes
|
- [Fehlender Merkmalstext TAK_ABN528_001_000]
|
Yes
|
- [Fehlender Merkmalstext TAK_ABN530_001_000]
|
Yes
|
- [Fehlender Merkmalstext TAK_ABN532_001_000]
|
Yes
|
- [Fehlender Merkmalstext TAK_ABN534_001_000]
|
Yes
|
- Collective error SF (red)
|
Yes
|
- Monitoring 24 V voltage supply ON (green)
|
Yes
|
Isolation
|
|
Isolation checked with
|
500 VDC
|
Isolation
|
|
between load voltage and all other switching components
|
Yes
|
between PROFIBUS DP all all other circuits
|
Yes
|
Permissible potential difference
|
|
between different circuits
|
75 VDC / 60 VAC
|
Dimensions
|
|
Dimensions
|
|
|
DP master module: 35 mm
|
|
119.5 mm
|
|
75 mm
|
Weights
|
|
|
320 g; DP master module: Approx. 100 g
|