ОбзорA decoupling module must be used:
If a mixed configuration is planned with temperature module, digital module and current measuring module or current/voltage measuring module, it must be checked first whether a decoupling module is required. If (Number (temperature module) * 2 + Number (digital module) * 1 + Number (current measuring module or current/voltage measuring module) * 4) > 14, a decoupling module is then required. For a calculation example, see the "SIPLUS HCS300I Heater Controller" System Manual, http://support.automation.siemens.com/WW/view/en/54439691. Note: For this equation, each module type is weighted with a specific current factor, see Table.
|
![]() |