Connection for power section supply and electronics power
- Suppply phase L1
- Suppply phase L2 or N
|
1
2
|
Rated DC voltages;
2-ph. AC 50/60 Hz 400 V +10 – 15 %
or
2-ph. AC 50/60 Hz 230 V +10 – 15 %
(see also terminals 14/15/16)
Fuse 2 x 5SD420
|
Unit ground connection
|
5
|
|
Control voltage connection
for field weakening
- Ground potential
- Ext. voltage E
|
6
7
|
0 V
0 V ... + 10 V
(only field weakening possible)
|
Field current monitoring
(floating)
|
9
10
|
1 NO contact: max.
AC 230 V/2.5 A
Contact opens at a field
current < 80 mA
|
Field winding connection
- Connection C2 (+)
- Connection D2 (-)
|
11
12
|
Rated DC voltages:
325 V DC at a rated supply voltage of
2-ph. AC 230 V;
max. field current: 3 A
|
Adaptation to rated supply voltages of 2-ph. 400 V or 2-ph.
AC 230 V (external jumpers)
|
14
15
16
|
Jumper 15 – 16 for a rated supply voltage von 2-ph. AC 400 V;
Jumper 15 – 14 at a
rated supply voltage of 2 -ph. 230 V.
|