Input
|
|
Resistance thermometer
|
|
Measured variable
|
Temperature
|
Sensor type
|
|
|
Pt25 … Pt1000
|
- To JIS C 1604; a=0.00392 K-1
|
Pt25 … Pt1000
|
|
Ni25 … Ni1000
|
Units
|
°C and °F
|
Connection
|
|
|
1 resistance thermometer (RTD) in 2-wire, 3-wire or 4-wire system
|
- Generation of average value
|
Series or parallel connection of several resistance thermometers in a two-wire system for the generation of average temperatures or for adaptation to other device types
|
|
2 resistance thermometers (RTD) in 2-wire system (RTD 1 – RTD 2 or RTD 2 – RTD 1)
|
Interface
|
|
|
Parameterizable line resistance ≤ 100 Ω (loop resistance)
|
|
No balancing required
|
|
No balancing required
|
Sensor current
|
≤ 0.45 mA
|
Response time
|
≤ 250 ms for 1 sensor with open-circuit monitoring
|
Open-circuit monitoring
|
can be switched off
|
Short-circuit monitoring
|
can be switched off (value is adjustable)
|
Measuring range
|
Parameterizable (see Table "Digital measuring errors")
|
Min. measured span
|
10 °C (18 °F)
|
Characteristic curve
|
Temperature-linear or special characteristic
|
Resistance-based sensors
|
|
Measured variable
|
Actual resistance
|
Sensor type
|
Resistance-based, potentiometers
|
Units
|
Ω
|
Connection
|
|
|
1 resistance-based sensor (R) in 2-wire, 3-wire or 4-wire system
|
- Generation of average value
|
2 resistance-based sensors in 2-wire system for generation of average value
|
|
2 resistance-based sensor in 2-wire system (R 1 – R 2 or R 2 – R 1)
|
Interface
|
|
|
Parameterizable line resistance ≤ 100 Ω (loop resistance)
|
|
No balancing required
|
|
No balancing required
|
Sensor current
|
≤ 0.45 mA
|
Response time
|
≤ 250 ms for 1 sensor with open-circuit monitoring
|
Open-circuit monitoring
|
can be switched off
|
Short-circuit monitoring
|
can be switched off (value is adjustable)
|
Measuring range
|
Parameterizable (see Table "Digital measuring errors")
|
Min. measured span
|
5 Ω ... 25 Ω (see Table "Digital measuring errors")
|
Characteristic curve
|
Resistance-linear or special characteristic
|
Thermocouples
|
|
Measured variable
|
Temperature
|
Sensor type (thermocouples)
|
|
|
Pt30Rh-Pt6Rh to DIN IEC 584
|
|
W5 %-Re acc. to ASTM 988
|
|
W3 %-Re acc. to ASTM 988
|
|
NiCr-CuNi to DIN IEC 584
|
|
Fe-CuNi to DIN IEC 584
|
|
NiCr-Ni to DIN IEC 584
|
|
Fe-CuNi to DIN 43710
|
|
NiCrSi-NiSi to DIN IEC 584
|
|
Pt13Rh-Pt to DIN IEC 584
|
|
Pt10Rh-Pt to DIN IEC 584
|
|
Cu-CuNi to DIN IEC 584
|
|
Cu-CuNi to DIN 43710
|
Units
|
°C or °F
|
Connection
|
|
|
1 thermocouple (TC)
|
- Generation of average value
|
2 thermocouples (TC)
|
|
2 thermocouples (TC)
(TC 1 – TC 2 or TC 2 – TC 1)
|
Response time
|
≤ 250 ms for 1 sensor with open-circuit monitoring
|
Open-circuit monitoring
|
can be switched off
|
Cold junction compensation
|
|
|
With integrated Pt100 resistance thermometer
|
|
With external Pt100 IEC 60751 (2-wire or 3-wire connection)
|
|
Cold junction temperature can be set as fixed value
|
Measuring range
|
Parameterizable (see Table "Digital measuring errors")
|
Min. measured span
|
Min. 50 ... 100 °C (90 ... 180 °F) (see Table "Digital measuring errors")
|
Characteristic curve
|
Temperature-linear or special characteristic
|
mV sensor
|
|
Measured variable
|
DC voltage
|
Sensor type
|
DC voltage source (DC voltage source possible over an externally connected resistor)
|
Units
|
mV
|
Response time
|
≤ 250 ms for 1 sensor with open-circuit monitoring
|
Open-circuit monitoring
|
can be switched off
|
Short-circuit monitoring
|
can be switched off (value is adjustable)
|
Measuring range
|
-10 ... 70 mV
-100 ... 1100 mV
|
Min. measured span
|
2 mV or 20 mV
|
Overload capability of the input
|
-1.5 ... +3.5 V DC
|
Input resistance
|
≤ 1 MΩ
|
Characteristic curve
|
Voltage-linear or special characteristic
|
Output
|
|
Output signal
|
4 ... 20 mA, 2-wire
|
Communication with SITRANS TH300
|
acc. to HART Rev. 5.9
|
digital display
|
|
Digital display (optional)
|
In current loop
|
Display
|
Max. 5 digits
|
Digit height
|
9 mm (0.35“)
|
Display range
|
-99999 ... + 99999
|
Units
|
any (max. 5 char.)
|
Setting:
Zero point, full-scale value and unit
|
over 3 keys
|
Load voltage
|
2.1 V
|
Measuring accuracy
|
|
Digital measuring errors
|
See "Digital measuring errors"
|
Reference conditions
|
|
|
24 V ± 1 %
|
|
500 Ω
|
|
23 °C (73.4 °F)
|
|
> 5 min
|
Error in the analog output (digital/analog converter)
|
< 0.1 % of span
|
Error due to internal cold junction
|
< 0.5 K (0.9 °F)
|
Temperature effect
|
< 0.1 % of max. span/10 °C (18 °F)
|
Auxiliary power supply effect
|
< 0.005 % of span/V
|
Long-term drift
|
|
|
< 0.02 % of span
|
|
< 0.03 % of span
|
|
< 0.04 % of span
|
Rated conditions
|
|
Ambient temperature
|
|
Storage temperature
|
-40 ... +85 °C (-40 ... 185 °F)
|
Condensation
|
Permissible
|
Electromagnetic compatibility
|
According to EN 61326 and NAMUR NE21
|
Degree of protection to EN 60529
|
IP67
|
Construction
|
|
Weight
|
Approx. 1.5 kg (3.3 lb) without options
|
Dimensions
|
See "Dimensional drawings"
|
Enclosure material
|
Die-cast aluminium, low in copper, GD‑AlSi 12 or stainless steel, polyester-based lacquer, stainless steel rating plate
|
Electrical connection, sensor connection
|
Screw terminals, cable inlet via M20 x 1.5 or ½-14 NPT screwed gland
|
Mounting bracket (optional)
|
Steel, galvanized and chrome-plated or stainless steel
|
Auxiliary power supply
|
|
Without digital display
|
DC 11 to 35 V (30 V with Ex)
|
With digital display
|
DC 13.1 to 35 V (30 V with Ex)
|
Electrically isolated
|
Between input and output
|
|
U eff = 1 kV, 50 Hz, 1 min
|
Certificates and approvals
|
|
Explosion protection ATEX
|
|
- "Intrinsic safety" type of protection
|
with digital display:
II 2 (1) G EEx ia IIC T4
without digital display:
II 2 (1) G EEx ia IIC T6
|
|
ZELM 99 ATEX 0007
|
- "Operating equipment that is non-ignitable and has limited energy for zone 2" type of protection
|
II 3G EEx nAL IIC T6/T4
|
|
ZELM 99 ATEX 0007
|
- "Flame-proof enclosure" type of protection
|
II 2 G EEx d IIC T5/T6
|
|
CESI 99 ATEX 079
|
Explosion protection to FM
|
Certificate of Compliance 3017742
|
- Identification (XP, DIP, NI, S)
|
- XP / I / 1 / BCD / T5 Ta = 85 °C (185 °F), T6 Ta = 50 °C (112 °F), Type 4X
|
|
- DIP / II, III / 1 / EFG / T5 Ta = 85 °C (185 °F), T6 Ta = 50 °C (112 °F), Type 4X
|
|
- NI / I / 2 / ABCD / T5 Ta = 85 °C (185 °F), T6 Ta = 50 °C (112 °F), Type 4X
|
|
- S / II, III / 2 / FG / T5 Ta = 85 °C (185 °F), T6 Ta = 50 °C (112 °F), Type 4X
|
Hardware and software requirements
|
|
- For the parameterization software SIPROM T for SITRANS TH200
|
|
|
PC with CD-ROM drive and USB/RS 232 interface
|
|
Windows 98, NT, 2000, XP
|
- For the parameterization software SIMATIC PDM for SITRANS TH300
|
See "Software", "SIMATIC PDM"
|
Communication
|
|
Load for HART connection
|
230 ... 1100 Ω
|
|
≤ 3.0 km (1.86 mi)
|
|
≤ 1.5 km (0.93 mi)
|
Protocol
|
HART protocol, version 5.9
|