Обзор
Обзор
The 2-track flowmeter SITRANS FUS380 comes as battery or mains powered and is designed to measure water flow in district heating plants, local networks, boiler stations, substations, chiller plants and other general water applications.
The type approved flowmeter version is named SITRANS FUE380 - see page 4/208.
Technically the meter types SITRANS FUS380 and SITRANS FUE380 are completely identical, only difference is the calibration limit and the type approval for custody transfer.
Область применения
The main application for SITRANS FUS380 is measurement of water flow or water flow in heat meter systems in district heating networks or chilled water.
Заказные данные
Аксессуары
Заказной № |
Вес, кг |
Описание |
Наличие на складе |
Заказать |
6ES7658-3HX06-0YA5 |
0.254 |
Simatic pdm, пакет для конфигурирования интеллектуальных устройств версии 6. 0 на одну точку (1 переменная), плавающая лицензия для 1 пользователя, инжен. прогр. обеспечение, прогр. обесп. и докум. на cd, ключ лицензии на fd, класс а, 5 языков (анг/нем/фран |
------ |
|
A5E00695277 |
0.175 |
Держатель для Irda интерфейс адапптера. Для SITRANS FUS080. |
------ |
|
A5E00730100 |
0.02 |
SITRANS FUS380 / FUE380 operating instr. En |
------ |
|
A5E00740611 |
0.02 |
SITRANS FUS380 / FUE380 operating instr. De |
------ |
|
A5E00754173 |
0.02 |
SITRANS FUS380 / FUE380 OP INSTR FR |
------ |
|
A5E00754188 |
0.02 |
SITRANS FUS380 / FUE380 OP INSTR ES |
------ |
|
A5E02328485 |
0.07 |
Sun cover for transmitter |
------ |
|
A5E02679676 |
0.19 |
Dual lithium battery pack 3.6 V, 34AH FOR: FUS080 AND FUE080. |
------ |
|
A5E02679923 |
0.055 |
Single lithium battery pack 3.6 V, 17 Ah for FUS080 and FUE080. |
------ |
|
FDK:087L4163 |
0.2 |
MAG8000 accessories USB Irda adapter |
------ |
|
FDK:087L4201 |
0.1 |
Battery backup for mains power supply, one pc. d-cell (3. 6 v, 16. 5 ah) |
------ |
|
FDK:087L4212 |
5 |
SITRANS FM, Accessories MAG 8000 RS 232 supplementary module point-to-point communication interface with Modbus RTU protocol |
------ |
|
FDK:087L4213 |
5 |
SITRANS FM, Accessories MAG 8000 RS485 supplementary module Multidrop communication interface with Modbus RTU protocol |
------ |
|
Тех. данные
Особенности
- Battery powered up to 6 years
- 115/230 V mains powered with back-up battery option in case of mains power failure
- Fast measuring frequency 20 Hz/0.5 Hz (230 V AC/Battery)
- Easy one button straight forward display
- 2-track measuring principle for optimum accuracy
- Compact or remote mounting
- Measures on all district water qualities and water conductivities
- No pressure drop
- Long-term stability
- 2 galvanic isolated digital outputs for easy connection to a calculator (potential free)
- Bidirectional measurement, with 2 totalizers and outputs
- Dynamic range Qmin:Qmax up to 1:400
- MODBUS RTU/RS 232, RS 485
Дизайн
The 2-track design of SITRANS FUS380 ensures maximum accuracy under short inlet conditions. The flowmeter consists of a flow sensor pipe, 4 transducers/transducer cables and a transmitter SITRANS FUS080.
The unit is available in a compact or a remote version with up to 30 meter distance from flowmeter to transmitter. When ordering a compact version the transducer cables are pre-mounted and ready for installation.
Compact mounting is only possible up to 120 °C (248 °F). The sensor must be isolated to protect transmitter from heat. The transmitter is available in an IP67/NEMA 4X/6 enclosure.
Интеграция
The flowmeter digital output is often used as input for an energy meter or as input for digital systems for remote reading.
SITRANS FUS380 has two digital output functions that can be individually selected, and optional MODBUS RTU communication modules.
Pulse output rate is defined when ordering.
If the flowmeter forms part of an energy meter system for custody transfer, no further approvals are needed, except eventually local approvals on the flowmeter.
Конфигурация
Configuration SITRANS FUS380
Selection guide SITRANS FUS380, standard version
DN
|
Qs (m3/h)
|
Qmax (m3/h) (105% of Qs)
|
Qp (m3/h)
|
Qi (m3/h) (1:100 of Qp)
|
Cutoff (m3/h) (50% of Qi)
|
Cutoff (% of Qmax)
|
Typical pulse value1) (l/pulse)
|
50
|
15
|
15,75
|
15
|
0,15
|
0,075
|
0,48
|
1
|
50
|
45
|
47,25
|
15
|
0,15
|
0,075
|
0,16
|
1
|
50
|
45
|
47,25
|
30
|
0,3
|
0,150
|
0,32
|
1
|
65
|
25
|
26,25
|
25
|
0,25
|
0,125
|
0,48
|
1
|
65
|
72
|
75,6
|
25
|
0,25
|
0,125
|
0,17
|
1
|
65
|
72
|
75,6
|
50
|
0,5
|
0,250
|
0,33
|
1
|
80
|
40
|
42
|
40
|
0,4
|
0,200
|
0,48
|
2.5
|
80
|
120
|
126
|
40
|
0,4
|
0,200
|
0,16
|
2.5
|
80
|
120
|
126
|
80
|
0,8
|
0,400
|
0,32
|
2.5
|
100
|
60
|
63
|
60
|
0,6
|
0,300
|
0,48
|
2.5
|
100
|
180
|
189
|
60
|
0,6
|
0,300
|
0,16
|
2.5
|
100
|
240
|
252
|
120
|
1,2
|
0,600
|
0,24
|
2.5
|
125
|
10
|
10,5
|
100
|
1
|
0,500
|
4,76
|
2.5
|
125
|
280
|
294
|
100
|
1
|
0,500
|
0,17
|
2.5
|
125
|
400
|
420
|
200
|
2
|
1,000
|
0,24
|
2.5
|
150
|
150
|
157,5
|
150
|
1,5
|
0,750
|
0,48
|
10
|
150
|
420
|
441
|
150
|
1,5
|
0,750
|
0,17
|
10
|
150
|
560
|
588
|
300
|
3
|
1,500
|
0,26
|
10
|
200
|
250
|
262,5
|
250
|
2,5
|
1,250
|
0,48
|
10
|
200
|
700
|
735
|
250
|
2,5
|
1,250
|
0,17
|
10
|
200
|
900
|
945
|
500
|
5
|
2,500
|
0,26
|
10
|
250
|
400
|
420
|
400
|
4
|
2,000
|
0,48
|
10
|
250
|
1120
|
1176
|
400
|
4
|
2,000
|
0,17
|
10
|
250
|
1400
|
1470
|
800
|
8
|
4,000
|
0,27
|
10
|
300
|
560
|
588
|
560
|
5,6
|
2,800
|
0,48
|
50
|
300
|
1560
|
1638
|
560
|
5,6
|
2,800
|
0,17
|
50
|
300
|
2100
|
2205
|
1120
|
11,2
|
5,600
|
0,25
|
50
|
350
|
750
|
787,5
|
750
|
7,5
|
3,750
|
0,48
|
50
|
350
|
2100
|
2205
|
750
|
7,5
|
3,750
|
0,17
|
50
|
350
|
2800
|
2940
|
1500
|
15
|
7,500
|
0,26
|
50
|
400
|
950
|
997,5
|
950
|
9,5
|
4,750
|
0,48
|
50
|
400
|
2660
|
2793
|
950
|
9,5
|
4,750
|
0,17
|
50
|
400
|
3600
|
3780
|
1900
|
19
|
9,500
|
0,25
|
50
|
500
|
1475
|
1548,75
|
1475
|
14,75
|
7,375
|
0,48
|
100
|
500
|
4130
|
4336,5
|
1475
|
14,75
|
7,375
|
0,17
|
100
|
500
|
5500
|
5775
|
2950
|
29,5
|
14,750
|
0,26
|
100
|
600
|
2150
|
2257,5
|
2150
|
21,5
|
10,750
|
0,48
|
100
|
600
|
6020
|
6321
|
2150
|
21,5
|
10,750
|
0,17
|
100
|
600
|
8000
|
8400
|
4300
|
43
|
21,500
|
0,26
|
100
|
700
|
2900
|
3045
|
2900
|
29
|
14,500
|
0,48
|
100
|
700
|
8120
|
8526
|
2900
|
29
|
14,500
|
0,17
|
100
|
700
|
10800
|
11340
|
5800
|
58
|
29,000
|
0,26
|
100
|
800
|
3800
|
3990
|
3800
|
38
|
19,000
|
0,48
|
100
|
800
|
10640
|
11172
|
3800
|
38
|
19,000
|
0,17
|
100
|
800
|
14200
|
14910
|
7600
|
76
|
38,000
|
0,25
|
100
|
900
|
5000
|
5250
|
3800
|
50
|
25,000
|
0,48
|
100
|
900
|
14000
|
14700
|
5000
|
50
|
25,000
|
0,17
|
100
|
900
|
20000
|
21000
|
5000
|
100
|
50,000
|
0,24
|
100
|
1000
|
6000
|
6300
|
3800
|
60
|
30,000
|
0,48
|
100
|
1000
|
16800
|
17640
|
6000
|
60
|
30,000
|
0,17
|
100
|
1000
|
24000
|
25200
|
12000
|
120
|
60,000
|
0,24
|
100
|
1200
|
9000
|
9450
|
3800
|
90
|
45,000
|
0,48
|
100
|
1200
|
25200
|
26460
|
9000
|
90
|
45,000
|
0,17
|
100
|
1200
|
36000
|
37800
|
18000
|
180
|
90,000
|
0,24
|
100
|
The values Qi, Qp and Qs are shown on the system label of the FUS380. Qi (Qmin) means the minimal and Qp (Qnom) the nominal flow rate. Qs is the highest operatable flow rate. The maximal flow rate (Qmax) is 105% of Qs. The low flow cut off is 50 % of Qi.
In order to obtain best pulse output resolution in the range Qmin to Qs of approx. 100 Hz at Qs, two or three flow values for every dimension can be selected at ordering. Therefore the ordering data table also shows Qp (Qn). This flow rate is between Qi (Qmin) and Qs and indicates the normal or typical flow.
1) Typical pulse values for SITRANS FUS380. Other pulse values are possible - see Selection and Ordering data table.
Технические данные
Pipe design
|
2-track sensor with flanges and integrated transducers wet calibrated from factory
|
Nominal size welded version
|
DN 50, 65, 80, 100, 125, 150, 200, 250, 300, 350, 400, 500, 600, 700, 800, 1000, 1200
|
Pressure rate
|
PN 16, PN 25, PN 40 EN 1092-1
|
Transducer design
|
Integrated version welded onto the pipe
|
Pipe material
|
- DN 100 ... 1200: Carbon Steel EN 1.0345 /P235 GH, painted in light-gray
|
|
- DN 50 ... 80: Die-cast bronze G-CuSn10/W2.1050.01 (EN 1982)
|
Transducer design
|
- DN 100 ... 1200: Integrated version and welded onto the pipe
|
|
- DN 50 ... 80: Screwed into the pipe
|
Transducer material
|
Stainless steel (AISI 316/1.4404)/brass (CuZn36Pb2as)
|
Sensor operating conditions
|
|
Storage
|
-40 … +85 °C (-40 … +185 °F)
|
Media/surface temperature
|
DN 100 ... 1200:
- Remote: 2 … 200 °C (35.6 … 392 °F)
|
|
DN 50 ... 80:
- Remote: 2 … 150 °C (35.6 … 302 °F)
|
|
DN 50 ... 1200:
- Compact: 2 … 120 °C (35.6 … 248 °F)
|
Degree of protection
|
Sensor connection IP67 / NEMA 4X/6
|
Max. flow velocity
|
DN 50 … 1200: 9 m/s (29.5 ft/s)
|
Transmitter
|
|
Display
|
LCD, 8 digits, additional 2 digits and symbols for status information
|
Push button
|
One push button for display information
|
Communication
|
IrDA – optical communication interface with MODBUS RTU protocol
|
|
Add-on modules:
- RS 232 serial interface with MODBUS RTU (Rx/Tx/GND), point to point with max. 15 m cable
- RS 485 serial interface with MODBUS RTU (+/-/GND), multi-drop with up to 32 devices with max. 1000 m cable
MODBUS RTU protocol is an open protocol (further information available on request)
Serial speed 1200, 2400, 4800, 9600, 19200, 38400 Baud
|
Enclosure
|
IP67/NEMA4X/6 to EN 60529 and DIN 40050
|
Temperature ambient
|
0 … 60 °C (32 … 140 °F)
|
Temperature storage
|
-40 … +85 °C (-40 … +185 °F) (battery included)
|
Installation
|
Compact on sensor: max. 120 °C (248 °F),
Separate: max. 30 m (98.4 ft) from transmitter
|
Mechanical vibration
|
2 g, 1 … 800 Hz sinusoidal in all directions to IEC 68-2-6
|
Design
|
Fibre-glass reinforced polyamide
|
Power supply
|
- Battery: replaceable 3.6 V LiSOCl (Lithium Thionyl Chloride) battery pack 32 Ah
- Mains: 85 … 265 V AC (50 … 60 Hz)
|
Measuring rate
|
Battery mode: 0.5 Hz
Mains supply: 20 Hz
Back-up mode: 0.5 Hz (at mains supply drop)
|
Digital output
|
Two passive individual galvanically isolated MOS relay outputs, A and B, max. ±35 V AC/DC, 50 mA
|
Max pulse frequency
|
100 Hz at Qmax
|
Alarm indication
|
Track 1 (F1), track 2 (F2), internal failure (F3, F4), Low battery indication (F5), Qmax overflow (F6), pulse overflow (F7, F8), internal data logger warning (F9)
|
Cable length
|
Max 30 m (98.4 ft) between transmitter and pipe
|
EMC
|
- Emission EN 61000-6-4
- Immunity EN 61000-6-2
|
|
FUS380
|
Flow value setting
|
Predefined settings according to dimension
|
Approval
|
No approval
|
Flow rate vf
|
0.02 … 9 m/s (0.065 … 29.5 ft/s)
|
Output A
|
Pulse: forward, reverse, forward net, reverse net (Preset: forward)
|
Output B
|
Pulse (forward, reverse, forward net, reverse net) alarm, call-up (Preset: alarm)
|
Pulse value A&B (depending on DN value)
|
0.1 l/p, 0.25 l/p, 0.5 l/p, 1 l/p, 2.5 l/p, 10 l/p, 25 l/p, 50 l/p, 100 l/p, 250 l/p, 500 l/p, 1 m3/p, 2.5 m3/p, 5 m3/p, 10 m3/p, 25 m3/p, 50 m3/p, 100 m3/p, 250 m3/p, 500 m3/p, 1000 m3/p
|
Pulse width
|
5/10/20/50/100/200/ 500 ms
|
Flow unit setup
|
Preset: m3/h
|
Volume unit setup
|
Preset: m3
|
SITRANS FUS380 uncertainty
To ensure continuous accurate measurement, flowmeters must be calibrated. The calibration is conducted at SIEMENS flow facilities accredited according to ISO/IEC 17025 by DANAK or UKAS.
The accreditation bodies DANAK and UKAS have signed the ILAC MRA agreement (International Laboratory Accreditation Corporation - Mutual Recognition Arrangement). Therefore the accreditation ensures international traceability and recognition of the test results in 39 countries world wide, including the US (NIST traceability).
A standard calibration certificate is shipped with every SITRANS FUS380.
Accuracy SITRANS FUS380:
Standard calibration: Better than 0.5 % of rate, 0.5 m/s < v < 8 m/s
v < 0.5 m/s, 0.5 + 0.25/v [%]
Output configuration SITRANS FUS380
Pulse volume: output A/B configured as volume per pulse, calculated on forward/reverse or net forward/reverse flow. The volume per pulse is free scaleable (via PDM software).
Pulse output B can be used as stated above or as alarm or call up function.
Call up: the call up output is active until manually reset by use of PDM program. The callup function is activated when an alarm is activated.
Дополнительно
Accessories and spare parts to Flowmeter FUS380 and FUE380
Type/description
|
Order No.F)
|
|
Dual battery pack (6 year lifetime) 33 Ah
|
FDK-087H2255
|

|
Single battery back-up to main supply 13.5 Ah
|
FDK-087L4201
|

|
Battery cover for transmitter FUS080
|
A5E00694468
|

|
PG 13.5 set (2 pcs.) for main cable/pulse cable
|
FDK-083G0228
|

|
PG 13.5 set (2 pcs.) for dual coax cable (6 mm)
|
A5E00694500
|
SITRANS FUS/FUE380 wall mounting kit for remote transmitter mounting, including connection plate (DN 50 ... 1200/2” ... 48”)
|
A5E00694509
|

|
SITRANS FUS/FUE380 terminal box for compact transmitter mounting, including connection plate, (bronze sensors only, DN 50 ... 80/2” ... 3”)
|
A5E01208138
|

|
SITRANS FUS/FUE380 terminal box for compact transmitter mounting, including connection plate, (steel sensors only, DN 100 ... 1200/4” ... 48”)
|
A5E00694660
|
Brace (holder) for optical IrDA eye
|
A5E00695277
|

|
IrDA infrared interface adapter with USB for data acquisition with 1.2 m (3.9 ft) cable
|
FDK-087L4163
|

|
RS 232 add-on module, point to point communication interface with MODBUS RTU protocol
|
FDK-087L4212
|

|
RS 485 add-on module, multidrop communication interface with MODBUS RTU protocol
|
FDK-087L4213
|
5 m (16.4 ft) cable set (4 pcs.) for DN 50 ... 80 (2“ ... 3“) remote mounting
|
A5E01208092
|

|
10 m (32.8 ft) cable set
(4 pcs.) for DN 50 ... 80 (2“ ... 3“) remote mounting
|
A5E01208114
|
20 m (65.6 ft) cable set
(4 pcs.) for DN 50 ... 80 (2“ ... 3“) remote mounting
|
A5E01208117
|
30 m (98.4 ft) cable set
(4 pcs.) for DN 50 ... 80 (2“ ... 3“) remote mounting
|
A5E01208121
|
1 m (3.28 ft) cable set
(4 pcs.) for DN 50 ... 80 (2“ ... 3“) for compact version
|
A5E01208126
|
5 m (16.4 ft) cable set (4 pcs.) for DN 100 ... 1200 (4“ ... 48“) remote mounting
|
A5E00695476
|
10 m (32.8 ft) cable set
(4 pcs.) for DN 100 ... 1200 (4“ ... 48“) remote mounting
|
A5E00695479
|
20 m (65.6 ft) cable set
(4 pcs.) for DN 100 ... 1200 (4“ ... 48“) remote mounting
|
A5E00695480
|
30 m (98.4 ft) cable set
(4 pcs.) for DN 100 ... 1200 (4“ ... 48“) remote mounting
|
A5E00695483
|
1 m (3.28 ft) cable set
(4 pcs.) for DN 100 ... 1200 (4“ ... 48“) for compact version
|
A5E00695486
|
Process Device Manager SIMATIC PDM
|
SIMATIC PDM Single Point V6.0
For operation and parameterization of one field device, communication using PROFIBUS DP/PA or HART modem, incl. 1 TAG
Cannot be expanded by further functions or TAG option/power-pack 5 languages (German, English, French, Spanish, Italian) executes with Windows 2000 Professional or Windows XP Professional
|
6ES7658-3HX06-0YA5
|

|
Downloads for DEVICE description FUE380 http:/support.automation.siemens.com/WW/view/en/17320235
F) All products on this page subject to export regulations AL: 9I999, ECCN: N.
Тех. данные 2
Чертеж
Transmitter IP67/NEMA 4X/6, wall mounting
Pipe Dimensions
Size
|
PN 16
|
PN 25
|
PN 40
|
|
|
|
|
|
L
|
Weight
|
L
|
Weight
|
L
|
Weight
|
A1
|
D
|
D1
|
Lift hug
|
DN
|
mm
|
kg
|
mm
|
kg
|
mm
|
kg
|
mm
|
mm
|
mm
|
|
50
|
-
|
-
|
-
|
-
|
300 +0/-2
|
10
|
320
|
165
|
125
|
No
|
65
|
-
|
-
|
-
|
-
|
300 +0/-2
|
15
|
330
|
185
|
145
|
No
|
80
|
-
|
-
|
-
|
-
|
350 +0/-3
|
18
|
350
|
200
|
160
|
No
|
100
|
350 +0/-2
|
20
|
-
|
-
|
350 +0/-2
|
16.5
|
361
|
220
|
180
|
No
|
125
|
350 +0/-2
|
23
|
-
|
-
|
350 +0/-3
|
53
|
374
|
250
|
210
|
No
|
150
|
500 +0/-3
|
26
|
-
|
-
|
500 +0/-3
|
32
|
388
|
285
|
240
|
Yes
|
200
|
500 +0/-3
|
38
|
500 +0/-3
|
47
|
500 +0/-3
|
55
|
414
|
340
|
295
|
Yes
|
250
|
600 +0/-3
|
60
|
600 +0/-3
|
76
|
600 +0/-3
|
91
|
440
|
405
|
355
|
Yes
|
300
|
500 +0/-3
|
66
|
500 +0/-3
|
81
|
-
|
-
|
466
|
460
|
410
|
Yes
|
350
|
550 +0/-3
|
94
|
550 +0/-3
|
121
|
-
|
-
|
-
|
-
|
-
|
-
|
400
|
550 +0/-3
|
124
|
550 +0/-3
|
153
|
-
|
-
|
507
|
580
|
525
|
Yes
|
500
|
625 +0/-3
|
190
|
625 +0/-3
|
244
|
-
|
-
|
558
|
715
|
650
|
Yes
|
600
|
750 +0/-3
|
303
|
750 +0/-3
|
365
|
-
|
-
|
609
|
840
|
770
|
Yes
|
700
|
875 +0/-3
|
361
|
875 +0/-3
|
552
|
-
|
-
|
660
|
910
|
840
|
Yes
|
800
|
1000 +0/-3
|
494
|
1000 +0/-3
|
770
|
-
|
-
|
710
|
1025
|
950
|
Yes
|
900
|
1230 +0/-6
|
475
|
1300 +6/-6
|
835
|
-
|
-
|
810
|
1125
|
1050
|
Yes
|
1000
|
1300 +0/-6
|
594
|
1370 +6/-6
|
1078
|
-
|
-
|
910
|
1255
|
1170
|
Yes
|
1200
|
1360+0/-6
|
732
|
-
|
-
|
-
|
-
|
1100
|
1485
|
1390
|
Yes
|
Size
|
PN 16
|
PN 25
|
PN 40
|
|
|
|
|
|
L
|
Weight
|
L
|
Weight
|
L
|
Weight
|
A1
|
D
|
D1
|
Lift hug
|
inch
|
inch
|
lb
|
inch
|
lb
|
inch
|
lb
|
inch
|
inch
|
inch
|
|
2
|
-
|
-
|
-
|
-
|
12 +0/-0.08
|
22
|
12.8
|
6.6
|
5
|
No
|
2½
|
-
|
-
|
-
|
-
|
12 +0/-0.08
|
33
|
13.2
|
7.4
|
5.8
|
No
|
3
|
-
|
-
|
-
|
-
|
14 +0/-0.08
|
40
|
14
|
8
|
6.4
|
No
|
4
|
13.77 +0/-0.08
|
44
|
-
|
-
|
13.77 +0/-0.12
|
36
|
14.21
|
8.66
|
7.09
|
No
|
5
|
13.77 +0/-0.08
|
50
|
-
|
-
|
13.77 +0/-0.12
|
117
|
14.72
|
9.84
|
8.27
|
No
|
6
|
19.68 +0/-0.12
|
57
|
-
|
-
|
19.68 +0/-0.12
|
71
|
15.28
|
11.22
|
9.45
|
Yes
|
8
|
19.68 +0/-0.12
|
84
|
19.68 +0/-0.12
|
104
|
19.68 +0/-0.12
|
121
|
16.30
|
13.39
|
11.61
|
Yes
|
10
|
23.62 +0/-0.12
|
132
|
23.62 +0/-0.12
|
168
|
23.62 +0/-0.12
|
201
|
17.32
|
15.94
|
13.98
|
Yes
|
12
|
19.68 +0/-0.12
|
146
|
19.68 +0/-0.12
|
179
|
-
|
-
|
18.35
|
18.11
|
16.14
|
Yes
|
14
|
21.65 +0/-0.12
|
207
|
21.65 +0/-0.12
|
267
|
-
|
-
|
-
|
-
|
-
|
-
|
16
|
21.65 +0/-0.12
|
273
|
21.65 +0/-0.12
|
337
|
-
|
-
|
19.96
|
22.83
|
20.67
|
Yes
|
20
|
24.61 +0/-3
|
419
|
24.61 +0/-3
|
538
|
-
|
-
|
21.97
|
28.15
|
25.59
|
Yes
|
24
|
29.53 +0/-0.12
|
668
|
29.53 +0/-0.12
|
805
|
-
|
-
|
23.98
|
33.07
|
30.31
|
Yes
|
28
|
34.45 +0/-0.12
|
796
|
34.45 +0/-0.12
|
1217
|
-
|
-
|
25.98
|
35.83
|
33.07
|
Yes
|
32
|
39.37 +0/-0.12
|
1089
|
39.37 +0/-0.12
|
1698
|
-
|
-
|
27.95
|
40.35
|
37.40
|
Yes
|
36
|
39.2 +0/-0.24
|
1047
|
52 +0/-0.24
|
1841
|
-
|
-
|
32.4
|
45
|
42
|
Yes
|
40
|
52 +0/-0.24
|
1309
|
54.8 +0/-0.12
|
2376
|
-
|
-
|
36.4
|
50.2
|
46.8
|
Yes
|
48
|
54.4 +0/-0.24
|
1614
|
-
|
-
|
-
|
-
|
44.4
|
59.4
|
55.6
|
Yes
|
Notes:
Weight for transmitter/electronics 1.5 kg (3.3 lb)
D and D1 are values for standard versions (with standard flanges). For versions with higher pressure ratings see EN 1092-1.
- not available
Схема подключения
The scheme shows the transducer cable connections between transmitter terminals and respective transducer and the electrical connection of the energy calculator SITRANS FUE950.
|
|