The SITRANS TF temperature transmitter works where others can't cope.
Область применения
The SITRANS TF can be used everywhere where temperatures need to be measured under particularly harsh conditions. Which is why users from all industries have opted for this field device. The rugged enclosure protects the electronics. The stainless steel model is even resistant to sea water and other aggressive elements. The inner workings offer high measuring accuracy, universal input and a wide range of diagnostic options.
Заказные данные
Заказной № |
Вес, кг |
Описание |
Наличие на складе |
Заказать |
7NG3137-..... |
1.5 |
SITRANS TF — ИЗМЕРИТЕЛЬНЫЙ ПРЕОБРАЗОВАТЕЛЬ ТЕМПЕРАТУРЫ В КОРПУСЕ ДЛЯ УСТАНОВКИ В ПРОИЗВОДСТВЕННЫХ УСЛОВИЯХ, С ПЕРЕДАЧЕЙ ИНФОРМАЦИИ ПО ПРОМЫШЛЕННОЙ СЕТИ FIELDBUS И ГАЛЬВАНИЧЕСКОЙ РАЗВЯЗКОЙ, С ДОКУМЕНТАЦИЕЙ НА КОМПАКТ-ДИСКЕ. ВСТРОЕННЫЙ ИЗМЕРИТЕЛЬНЫЙ ПРЕОБРАЗОВАТЕЛЬ: SITRANS TH400 С ПОДДЕРЖКОЙ СЕТИ PROFIBUS PA. |
------ |
Уточните конфигурацию
|
7NG3138-..... |
1.5 |
SITRANS TF — ИЗМЕРИТЕЛЬНЫЙ ПРЕОБРАЗОВАТЕЛЬ ТЕМПЕРАТУРЫ В КОРПУСЕ ДЛЯ УСТАНОВКИ В ПРОИЗВОДСТВЕННЫХ УСЛОВИЯХ, С ПЕРЕДАЧЕЙ ИНФОРМАЦИИ ПО ПРОМЫШЛЕННОЙ СЕТИ FIELDBUS, С ГАЛЬВАНИЧЕСКОЙ РАЗВЯЗКОЙ, С ДОКУМЕНТАЦИЕЙ НА КОМПАКТ-ДИСКЕ. ВСТРОЕННЫЙ ИЗМЕРИТЕЛЬНЫЙ ПРЕОБРАЗОВАТЕЛЬ: SITRANS TH400 С ПОДДЕРЖКОЙ ПРОМЫШЛЕННОЙ СЕТИ FIELDBUS. |
------ |
Уточните конфигурацию
|
Тех. данные
Особенности
- For universal use as a transmitter for resistance thermometers, thermocouple elements, Ω or mV signals
- Rugged two-chamber enclosure in die-cast aluminium or stainless steel
- Degree of protection IP67
- Can be mounted elsewhere if the measuring point
- is not easily accessible
- is subject to high temperatures
- is subject to vibrations from the system
- or if you want to avoid long neck tubes and/or protective tubes
- Can be mounted directly on American-design sensors
- Wide range of approvals for use in potentially explosive atmospheres. "Intrinsically safe, non-sparking and flameproof" type of protection, for Europe and USA
Функции
Features
General
- Polarity-neutral bus connection
- 24-bit analog-digital converter for high resolution
- Electrically isolated
- Version for use in hazardous areas
- Special characteristic
- Sensor redundance
Transmitter with PROFIBUS PA communication
- Function blocks: 2 x analog
Transmitter with FOUNDATION fieldbus communication
- Function blocks: 2 x analog and 1 x PID
- Functionality: Basic or LAS
Mode of operation
The following function diagram explains the mode of operation of the transmitter.
The only difference between the two versions of the SITRANS TF (7NG3137-... and 7NG3138-...) is the type of field bus protocol used (PROFIBUS PA or FOUNDATION fieldbus).
SITRANS TF with TH400, function diagram
System communication
SITRANS TF with TH400, communication interface
Технические данные
Input
|
|
Analog/digital conversion
|
|
|
< 50 ms
|
|
24-bit
|
Resistance thermometer
|
|
Pt25 ... Pt1000 to IEC 60751/JIS C 1604
|
|
|
-200 ... +850 °C (-328 ... +1562 °F)
|
Ni25 ... Ni1000 to DIN 43760
|
|
|
-60 ... +250 °C (-76 ... +482 °F)
|
Cu10 ... Cu1000, α = 0.00427
|
|
|
-50 ... +200 °C (-58 ... +392 °F)
|
Line resistance per sensor cable
|
Max. 50 Ω
|
Sensor current
|
Nominal 0.2 mA
|
Sensor fault detection
|
|
|
Yes
|
- Sensor short-circuit detection
|
Yes, < 15 Ω
|
Resistance-based sensors
|
|
Measuring range
|
0 Ω ... 10 kΩ
|
Line resistance per sensor cable
|
Max. 50 Ω
|
Sensor current
|
Nominal 0.2 mA
|
Sensor fault detection
|
|
|
Yes
|
- Sensor short-circuit detection
|
Yes, < 15 Ω
|
Thermocouple
|
|
to IEC 584
|
Measuring range
|
|
400 ... 1820 °C (752 ... 3308 °F)
|
|
-100 ... +1000 °C (-148 ... +1832 °F)
|
|
-100 ... +1000 °C (-148 ... +1832 °F)
|
|
-100 ... +1200 °C (-148 ... +2192 °F)
|
|
-180 ... +1300 °C (-292 ... +2372 °F)
|
|
-50 ... +1760 °C (-58 ... +3200 °F)
|
|
-50 ... +1760 °C (-58 ... +3200 °F)
|
|
-200 ... +400 °C (-328 ... +752 °F)
|
to DIN 43710
|
|
|
-200 ... +900 °C (-328 ... +1652 °F)
|
|
-200 ... +600 °C (-328 ... +1112 °F)
|
to ASTM E988-90
|
|
|
0 ... 2300 °C (32 ... 4172 °F)
|
|
0 ... 2300 °C (32 ... 4172 °F)
|
External cold junction compensation
|
-40 ... +135 °C (-40 ... +275 °F)
|
Sensor fault detection
|
|
|
Yes
|
- Sensor short-circuit detection
|
Yes, < 3 mV
|
- Sensor current in the event of open-circuit monitoring
|
4 μA
|
mV sensor - voltage input
|
|
Measuring range
|
-800 ... +800 mV
|
Input resistance
|
10 MΩ
|
Output
|
|
Filter time (programmable)
|
0 ... 60 s
|
Update time
|
< 400 ms
|
Measuring accuracy
|
|
|
Accuracy is defined as the higher value of general values and basic values.
|
General values
|
|
|
Type of input
|
Absolute accuracy
|
Temperature coefficient
|
All
|
≤ ±0.05 % of measured value
|
≤ ±0.002 % of measured value/°C
|
Basic values
|
|
|
Type of input
|
Basic accuracy
|
Temperature coefficient
|
Pt100 and Pt1000
|
≤ ±0.1 °C
|
≤ ±0.002 °C/°C
|
Ni100
|
≤ ±0.15 °C
|
≤ ±0.002 °C/°C
|
Cu10
|
≤ ±1.3 °C
|
≤ ±0.02 °C/°C
|
Resistance-based sensors
|
≤ ±0.05 °Ω
|
≤ ±0.002 Ω/°C
|
Voltage source
|
≤ ±10 μV
|
≤ ±0.2 μV/°C
|
Thermocouple, type:
E, J, K, L, N, T, U
|
≤ ±0.5 °C
|
≤ ±0.01 °C/°C
|
Thermocouple, type:
B, R, S, W3, W5
|
≤ ±1 °C
|
≤ ±0.025 °C/°C
|
Cold junction compensation
|
≤ ±0.5 °C
|
|
Reference conditions
|
|
|
Warming-up time
|
30 s
|
|
Signal-to-noise ratio
|
Min. 60 dB
|
|
Calibration condition
|
20 ... 28 °C (68 ... 82 °F)
|
|
Conditions of use
|
|
Ambient conditions
|
|
Permissible ambient temperature
|
-40 ... +85 °C (-40 ... +185 °F)
|
Permissible storage temperature
|
-40 ... +85 °C (-40 ... +185 °F)
|
Relative humidity
|
≤ 98 %, with condensation
|
Insulation resistance
|
|
|
500 V AC for 60 s
|
|
50 V AC/75 V DC
|
Electromagnetic Compatibility
|
|
NAMUR
|
NE21
|
EMC 2004/108/EC Emission and Noise Immunity
|
EN 61326-1, EN 61326-2-5
|
Construction
|
|
Weight
|
Approx. 1.5 kg (3.3 lb) without options
|
Dimensions
|
See "Dimensional drawings"
|
Enclosure materials
|
- Die-cast aluminium, low in copper, GD‑AlSi 12 or stainless steel
- Polyester-based lacquer for GD AlSi 12 enclosure
- Stainless steel rating plate
|
Electrical connection, sensor connection
|
- screw terminals
- Cable inlet via M20 x 1.5 or ½-14 NPT screwed gland
- Bus connection with M12 plug (optional)
|
Mounting bracket (optional)
|
Steel, galvanized and chrome-plated or stainless steel
|
Degree of protection
|
IP67 to EN 60529
|
Auxiliary power supply
|
|
Power supply
|
|
- Standard, Ex "d", Ex "nA", Ex "nL", XP, NI
|
10.0 ... 32 V DC
|
|
10.0 ... 30 V DC
|
- In FISCO/FNICO installations
|
10.0 ... 17.5 V DC
|
Power consumption
|
< 11 mA
|
Max. increase in power consumption in the event of a fault
|
< 7 mA
|
Certificates and approvals
|
|
Explosion protection ATEX
|
|
EC type test certificate
|
ZELM 99 ATEX 0007
|
- Type of protection "intrinsic safety i"
(version: 7NG313x-1xxxx)
|
II 2(1) G Ex ia IIC T4/T6
|
Conformity statement
|
ZELM 07 ATEX 3349
|
- "Operating equipment that is non-ignitable and has limited energy" type of protection
(version: 7NG313x-2xxxx)
|
II 3 G Ex nA [nL] IIC T4/T6
II 3 G Ex nL IIC T4/T6
|
EC type test certificate
|
CESI 99 ATEX 079
|
- "Flame-proof enclosure" type of protection (version: 7NG313x-4xxxx)
|
II 2 G Ex d IIC T5/T6
|
Explosion protection: FM for USA
|
|
|
FM 3017742
|
- Type of protection XP, DIP, NI and S
(version 7NG313x-5xxxx)
|
- XP / I / 1 / BCD / T5,T6; Type 4X
- DIP / II, III / 1 / EFG / T5,T6; Type 4X
- NI / I / 2 / ABCD / T5,T6; Type 4X
- S / II, III / 2 / FG T5,T6; Type 4X
|
Communication
|
|
Parameterization interface
|
|
|
|
|
A&D profile, Version 3.0
|
|
EN 50170 Volume 2
|
|
126
|
|
2 x analog
|
- FOUNDATION fieldbus connection
|
|
|
FF protocol
|
|
FF design specifications
|
|
Basic or LAS
|
|
ITK 4.6
|
|
2 x analog and 1 x PID
|
Factory setting
|
for SITRANS TH400 PA
|
|
Sensor
|
Pt100 (IEC)
|
Type of connection
|
3-wire circuit
|
Unit
|
°C
|
Failure mode
|
Last valid value
|
Filter time
|
0 s
|
PA address
|
126
|
PROFIBUS Ident No.
|
Manufacturer-specific
|
for SITRANS TH400 FF
|
|
Sensor
|
Pt100 (IEC)
|
Type of connection
|
3-wire circuit
|
Unit
|
°C
|
Failure mode
|
Last valid value
|
Filter time
|
0 s
|
Node address
|
22
|
Чертеж
SITRANS TF with TH400, dimensions in mm (inches)
Схема подключения
SITRANS TF with TH400, sensor connection assignment
|
|