Design, mounting
|
Terminal housing for
mounting on 35 mm standard rail to DIN 46227 and DIN EN 50022
|
Terinals
|
Screw terminals
max. conductor cross-section 2.5 mm2
|
Dimensions
|
H x W x D= 75 mm x 22.5 mm x 100 mm
|
Supply voltage
|
+ 24 V (+20 ... +30 V) external
|
Current consumption
|
45 mA max.
(if both branches are in operation)
|
Storage and transportation temperature
|
-50 ... +85 °C
|
Ambient temperature
|
0 ... 45 °C
|
Humidity rating
|
F
|
Circuit branch: current-voltage conversion
|
Input resistance
|
167.3 Ω (209.3 Ω for Live Zero
operation)
|
Input current
|
0 ... 20 mA (4 ... 20 mA for Live Zero
operation)
|
Output resistance
|
112 Ω
|
Output voltage
|
0 ... +10 V; 0 ... -10 V
(max. +11.5 V bzw. -11.5 V)
|
Max. output current
|
2 mA (^= 5 k Ω Lastwiderstand)
|
Short-circuit protection
|
continuous
|
Accuracy
|
±25 mV at 10 V (±30 mV for Live Zero
operation)
|
Zero point error
|
±10 mV (±20 mV mV for Live Zero
operation)
|
Circuit branch: voltage-current conversion
|
Input resistance
|
10 M Ω
|
Input voltage
|
0 ... +10 V; 0 ... -10 V
|
Output resistance
|
≤ 10 mV (±20 mV for Live Zero
operation)
|
Output current
|
0 ... 20 mA (4 ... 20 mA for Live Zero
operation)
|
Permissible load resistance
|
0 ... 700 Ω
|
Accuracy
|
±70 μA bei 20 mA (±80 μA for Live
Zero operation)
|
Zero point error
|
±20 μA (± 30 μA for Live Zero
operation)
|