SITRANS FUG1010
|
|
Input
|
|
Flow range
|
± 30 m/s (± 100 ft/s), bidirectional
|
Flow sensitivity
|
0.0003 m/s (0.001 ft/s), flow rate independent
|
Minimum pressure
|
7 … 10 bar (100 … 145 psi), typical (gas composition and application dependent; plastic pipes support operation at atmospheric pressure)
|
Pipe size
|
25 mm … 1.52 m (1”… 60“) (for other sizes, consult factory)
|
Analog inputs
|
Current: 4x 4 … 20 mA, programmable
(IP65 (NEMA 7) enclosure has 2x 4 … 20 mA, programmable))
|
Output
|
|
Standard outputs
|
- Current: 2x 4 … 20 mA, a programmable, standard
Additional 2x optional, except IP65 (NEMA 7)
- Voltage: 2x 0 … 10 V DC, menu programmable
(None for IP65 (NEMA 7) enclosure)
- 2x Open collector digital pulses (quadrature)
(None for IP65 (NEMA 7) enclosure)
- 2x 0 … 5 kHz, TTL pulse square wave +
(None for IP65 (NEMA 7) enclosure)
- 1x Optically isolated digital pulse & source, IP65 (NEMA 7) enclosure only
- RS232 Serial Port
|
Enhanced outputs
|
- MODBUS (RS485/422/232)
(not for IP65 (NEMA 7)
|
Status/Alarm I/O
|
- 4x programmable form C relays
(not for IP65 (NEMA 7) enclosure)
- 4x programmable N.O. Mer. Wet. Relays optional (not for IP65 (NEMA 7) enclosure)
- 2x Optically coupled output logic gates
(for IP65 (NEMA 7) enclosure, only)
- 1 Totalizer clear switch input
(not for IP65 (NEMA 4X))
- 1 Totalizer hold switch input
(not for IP65 (NEMA 7) enclosure)
- 1x Opto iso. totalizer clear switch input
(for IP65 (NEMA 7) enclosure, only)
- 1x Opto iso. totalizer hold switch input
(for IP 65 (NEMA 7) enclosure, only)
|
Accuracy
|
|
Typical accuracy
|
1 % … 2 % of actual volume reading (higher accuracy is pipe condition and flow profile dependent)
|
Repeatability
|
0.05 % … 0.1 %, of actual volume reading, for 1.5 … 30 m/s (5 … 100 ft/s) velocities (pipe condition dependent)
|
Zero drift
|
0.0003 m/s (0.001 ft/s), with ZeroMatic Path active
|
Data refresh rate
|
5 Hz (80 Hz optional)
|
Rated operation conditions
|
|
Degree of protection
|
|
|
IP65 (NEMA 4X)
|
|
IP65 (NEMA 7)
|
- Wall mount explosionproof
|
IP66 (NEMA 7)
|
Gas temperature
|
-40 … +60 °C (-40 … +140 °F) (for higher temperatures consult factory)
|
Ambient temperature
|
-18 … +60 °C (0 … 140 °F)
|
Design
|
|
Dimensions
|
see SITRANS F US Clamp-on "System info and selection guide"
|
Weight
|
see diagrams
|
Power supply
|
|
- For IP65 (NEMA 4X) and IP66 (NEMA 7)
|
- 90 … 240 V AC,
50 … 60 Hz (30 VA) or 9 … 36 V DC (12 W)
|
|
- 90 … 240 V AC,
50 … 60 Hz (15 VA) or 9 … 36 V DC (10 W)
|
Indication and operation
|
|
Data logger memory
|
1 Mbyte, programmable for 17 data functions
|
Display
|
|
- IP65 (NEMA 4X) and IP66 (NEMA 7) enclosures
|
128 x 240 pixel LCD with backlight
|
|
2 x 16 alphanumeric LCD display
|
Keypad
|
|
- IP65 (NEMA 4X) and IP66 (NEMA 7) enclosures
|
33 keypad buttons with tactile feedback
|
|
5 magnetic hall effect switches
|
Language options
|
English, Spanish, German, Italian, French
|
Certificates and approvals
|
|
IP65 (NEMA 4X) flow display computer ratings
|
FM and CSA
|
I.S. Class I, II, Div 1
N-I Class I, Div 2
S Class II, Div 2 (FM only)
|
ATEX
|
- Flowmeter:
Ex II (1) G [EEx ia] IIC
Ex II 3 (1) G EEx nC [ia] IIC T5
- Transducers:
Ex II 1 G EEx ia IIC T5
Ex II 2 G EEx m II T5 (for use with flowmeter in safe area)
|
CCOE (India)
|
EEx (ia)
|
INMETRO (Brazil)
|
- Flowmeter:
[BR-Ex ia] IIC
BR-Ex nC [ia] T5
- Transducers:
BR-Ex ia IIC T5 IP65
-50 °C ≤ Ta ≤ +60 °C
|
GoST
|
- Flowmeter:
[Exia] IIC
- Transducers:
Exia IIC T5
|
IP65 (NEMA 7) compact explosionproof enclosure ratings
|
FM and CSA
|
Ex Class I, Div 1
D-I Class II, Div 1
I.S. Class I, Div 1
N-I Class I, Div 2
S Class II, Div 2 (FM only)
|
ATEX
|
- Flowmeter:
Ex II 2 (1) G EEx d [ia] IIB + H2 T5
- Transducers:
Ex II 1 G EEx ia IIC T5
|
CCOE (India)
|
EEx d
|
INMETRO (Brazil)
|
- Flowmeter:
BR-Ex d [ia] IIB + H2 T5
- Transducers:
BR-Ex ia IIC T6 IP65
-50 °C ≤ Ta ≤ +60 °C
|
IP66 (NEMA 7) wall mount explosionproof enclosure ratings
|
FM and CSA
|
Ex Class I, Div 1
D-I Class II, Div 1
I.S. Class I, Div 1
N-I Class I, Div 2
S Class II, Div 2 (FM only)
|
ATEX
|
- Flowmeter:
Ex II (1) G [EEx ia] IIC
Ex II 3 (1) G EEx nC [ia] IIC T5
Ex II 2 (1) G EEx d [ia IIC] IIB+H2 T5
- Transducers:
Ex II 1 G EEx ia IIC T5
|
INMETRO (Brazil)
|
- Flowmeter:
[BR-Ex ia] IIC
BR-Ex nC [ia] IIC T5
BR-Ex d [ia IIC] IIB + H2 T5
- Transducers:
BR-Ex ia IIC T5 IP65
-50 °C ≤ Ta ≤ +60 °C
|