ОбзорBraking resistor for blocksize format, frame sizes FSA and FSC The PM340 Power Modules cannot regenerate into the line supply. For regenerative operation, e.g. the braking of a rotating mass, a braking resistor must be connected to convert the resulting energy into heat. The braking resistor is connected at terminals DCP/R1 and R2. The braking resistors can be installed at the side next to the PM340 Power Modules. The braking resistors for the FSA and FSB frame sizes are designed as base components. If the PM340 Power Modules of the FSA or FSB frame sizes are operated without line reactor, the braking resistors can also be installed under the Power Modules. The braking resistors for the Power Modules of the FSC to FSF frame sizes should be placed outside the control cabinet or the switchgear room in order to lead the resulting heat loss away from the Power Modules, thereby allowing a reduction in the level of air conditioning required. The braking resistors are designed with a temperature switch. The temperature switch must be evaluated to prevent consequential damage if the braking resistor overheats. Заказные данные
|
![]() |